Operation instructions
SIPOS SEVEN: PROFITRON, HiMod
Page 110 Y070.302/EN
13 Communication and data exchange
13
Communication and data exchange
13�4�5 Clone actuator
Only available in ‘Expert’ user level and in ‘LOCAL’ or ‘Off’ mode.
The ‘Clone actuator’ function is used to write all actuator parameter values (factory parameters
includingendpositionadjustment,parameterswhichcanbemodiedbythecustomerand
operating data such as motor operating hours, number of cut-offs, etc.), which were written to
theUSBashdrive(referto„13.4.2DownloadparameterstoUSBashdrive“onpage109),to
a ‘new’ electronics unit. In terms of the functions, the actuator with the ‘new’ electronics unit is a
duplicate of the ‘original actuator’.
This function enables quick and easy commissioning, for example after replacing the electronics
unit.
Fig� 1: Clone actuator procedure
Operation sequence
1. ConnectUSBashdrivetotheoriginalelec-
tronicsunitrefertog.,item1.
The‘USBashdrive’menuappears.
2. Select “Download parameters” from the
menu (item 2)andconrm.(referalsoto
„13.4.2DownloadparameterstoUSBash
drive“ on page 109.
The.STEleissavedtotheUSBashdrive.
Successfulsavingisconrmedviaames-
sage.
3. ConnectUSBashdrivetothe‘”new”re-
placementelectronicsunit(g.,item3). The
‘USBashdrive’menuappears.
4. Select“Cloneactuator”inthemenu(g.,
item 4)andconrm(2).Thedisplaychanges
tothe“Selectle”menu.
5. Select.STEleofthe‘originalactuator’and
conrm.
A note is displayed requesting you to verify
whether conversion rate and mains voltage
of the target actuator match.
6. If not, abort cloning selecting “No”. If yes,
continue cloning selecting “Yes”.
DataiswrittenfromtheUSBashdriveto
theactuator.Successfulcloningisconrmed
withamessage,refertog.3.
Fig� 2: Note: Check conversion rate and
mains voltage
Fig� 3: Message: Cloning successful