Parameters and possible parameter values
8 Parameters and possible parameter values
8�6 Special parameters
Intermediate contact CL
The signal is active from 0 % to the programmed value.
Setting range: 0 to 100 % of the travel
In the factory, 0 to 2 % are set for torque-dependent cut-off, 0 to 0 % for travel-dependent cut-
off.
Intermediate contact OP
The output signal is active from the programmed value to 100 %.
Setting range: 100 to 0 % of the travel
In the factory, 98 to 100 % are set for torque-dependent cut-off, 100 to 100 % for travel-depen-
dent cut-off.
8�6�4 Motor
Motor heating On/Off
To prevent condensation while the motor is at standstill, the motor can be heated with DC cur-
rent
when the heater is activated. The heating up depends on the difference between motor tem-
perature and ambient temperature.
Ifexposedtostrongclimaticuctuations,theactuatorshouldbeoperatedwiththemotorheater
switched on.
In the factory, the motor heater is set according to order.
Motor warning
If the temperature set here (within a range between 0 and 155 °C) is exceeded, a warning sig-
nalwillbeissued.Thewarningsignalcanbeprovidedviabinarysignalandeldbusprotocol.
For 2SG7, this parameterization is not available.
135 °C is set in the factory.
Motor protection on/off
The motor is equipped with full electronic
motor protection against thermal damage.
The motor protection is activated in the fac-
tory and can be disabled.
Disabling the motor protection will void
the warranty for the motor!
To prevent accidental disabling of the motor
protection, the information on the right will
bedisplayedandmustbeconrmed.
Motor
Motor heating
Motor warning
Motor protection
Fig�: Motor protection warning