the lower threshold is 3.6 mA,
■
the upper threshold for the failure
detection is 21 mA.
For analog inputs with this programming,
4– 20 mA signals outside these limits are de-
tected as failures (wire break).
Changing the lower and/or upper limit is only
reasonable for control systems whose signals
mightnotliewithintheNAMURspecication.
Lower threshold
Possible setting from 0.0 to 3.6 mA.
Upper threshold
Possible setting from 20.0 to 22.0 mA.
3.6 mA have been set for the lower threshold and 21 mA or the upper threshold in the factory.
This parameter is not applicable for “Split range function”.
Threshold open circuit analog input
Lower threshold
Upper threshold
8�6�10 Delay of Power Failure Message
If the mains voltage is outside the tolerance of
–30 %/+15 % , a fault signal is set. To prevent
faultsignalsforshort-termvoltageuctuations,
a delay time (duration of the power failure) can
bedenedafterwhichthefaultsignalwillbeis-
sued.Alsorefertogureontheright.
Delay
Possible setting for tolerance time: 0 to 25 s.
Factory setting is 6 s.
Fig�: Delay of Power failure message
Delay of Power failure message
X.X s
8�6�11 Torque measurement ange
Thismenuitemisusedtosetwhetheratorquemeasurementangeisactuallyavailableandifso,
where the signal cable is actually connected.
Torque measurement ange
Not valid
Analog input AI1
Analog input AI2
ThecurrentvaluecanbedisplayedviatheObserver>Statusmenu.Possiblyrequiredzeroadjust-
ments can also be performed via this menu , refer to „11.4 Torque zero adjustment“ on page 104.
8�6�12 Thresholds for detection of wire break at analog outputs
AccordingtoNAMURspecicationontheharmonizationofsignallevelsforthe4–20mAinter-
face,
Fig�: Threshold open circuit analog input