8 Parameters and possible parameter values
8.2 Valve-specic parameters
8
Parameters and possible parameter values
8�2�2 Parameters and their values in the ‘Valve’ menu
Unless stated otherwise during order, the following values/settings are set as default.
CLOSE direction parameter
Direction of rotation of the output drive shaft when closing. Possible setting: Clockwise or Counter-
clockwise.
If the closing direction was changed, the end positions must be set afterwards.
Speed parameter
= Speed in CLOSE direction. = Speed in OPEN direction
Parameterization within the speed range, refer to name plate.
Cut-off mode parameter
= Cut-off mode in end position CLOSED. = Cut-off mode in end position OPEN.
Possible setting: Clockwise or Counter-clockwise.
If the cut-off mode was changed, the end positions must be set afterwards.
Tripping torque parameter
= Tripping torque in end position CLOSED. = Tripping torque in end position OPEN.
Possible setting: in 10 % steps:
■
Actuators classes A and B (8 levels) from 30 % to 100 % M
trip
(default setting = 30 %)
■
Actuators classes C and D (6 levels) from 50 % to 100 % M
trip
(default setting = 50 %)
Cannot be set for 2SG7.
(Not for 2SQ7.)
CLOSE direction
Clockwise
Speed
14 rpm
14 rpm
Cut-off mode
Travel dependent
Travel dependent
(Not for 2SQ7.)
Tripping torque
20 Nm
20 Nm