EasyManua.ls Logo

SIPOS SEVEN 2SA7 - Adjust Mechanical Position Indicator; Position Indicator Symbols; Adjust Position Indicator; Position Indicator for 2 SG7

SIPOS SEVEN 2SA7
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Y070.302/EN Page 55
Operation instructions
SIPOS SEVEN: PROFITRON, HiMod
7
Commissioning
7 Commissioning
7�4 End positions– Signaling gear
7�4�5 Adjust mechanical position indicator
The mechanical position indicator indicates the valve position. The symbol stands for OPEN
and the
symbolforCLOSED(refertog.1,items1and2).
The mechanical position indicator is an option, and not included in all devices.
If the actuator was delivered mounted on a valve, the setting may already be performed by the
valve manufacturer. The setting must be checked during commissioning.
If the mechanical position indicator was not yet set with the end positions, set the indicator as fol-
lows.
Operation sequence
1. Operate the actuator into the end position
CLOSED.
2. Remove signaling gear cover.
3. Turnwhitediscwithredsymbol(g.2,
item1)untilthesymbolforCLOSED(g.1,
item 1) and the arrow (3) are aligned in the
indicator glass of the cover.
4. Operate actuator to position OPEN.
5. Holdwhitedisc(g.2,item1)inpositionand
turn transparent disc (2) until the green sym-
bolforOPEN(g.1,item2)andthearrow(3)
are aligned.
6. Fix signaling gear cover with screw while
heedingpropertoftheseal.
Fig� 1: Position indicator symbols
Fig� 2: Adjust position indicator
Fig� 3: Position indicator for 2SG7
Fig� 4: Position indicator for 2SQ7

Table of Contents