Commissioning
7 Commissioning
7�3 Valve parameters
7�3�2 Program speeds/positioning times
By programming the speeds, the speed of the actuator during closing, opening and approaching the
EMERGENCY position is determined.
Thespeedrangeofanactuatorisbasedonthesizing,denedbytheapplication.Refertoname
plate for the possible actuator speed.
The following values apply to the actuator (without additional gear).
Tripping torque
ranges [Nm]
Flange
Speed
ranges
[rpm]]
Standard output
speed [rpm]
without additional
gear
Classes A and B (type of duty in compliance with EN 15714-2)
3 ~ 380 – 460 V
1200 – 4000 F30
►
1.25 – 10 3.5
600 – 2000 F25 ► 2.5 – 20 7
300 – 1000 F16 ► 5 – 28 14
150 – 500 F14, F16 ► 5 – 40 14
75 – 250 F12, F14 ► 10 – 80 28
37 – 125 F10, F12, F14 ► 20 – 112 56
18 – 60 F10 ► 20 – 160 56
9 – 30 F7, F10
►
1 ~ 220 – 230 V / 3 ~ 190 – 200 V 5 – 40 14
37 – 125 F10, F12, F14 ► 10 – 80 28
18 – 60 F10 ► 20 – 160 56
9 – 30 F7, F10
►
20 – 112 56
1 ~ 110 – 115 V 5 – 20 14
37 – 112 F10, F12, F14 ► 10 – 40 28
18 – 60 F10 ► 20 – 56 56
9 – 30 F7, F10
►
20 – 80 56
Classes C and D (type of duty in compliance with EN 15714-2)
3 ~ 380 – 460 V
1400 – 2800 F30
►
1.25 – 10 3.5
700 – 1400 F25 ► 5 – 40 14
350 – 700 F16 ► 10 – 80 28
175 – 350 F14, 16 ►
87 – 175 F12, F14 ►
40 – 80 F10, F12, F14 ►
20 – 40 F10 ►
10 – 20 F07, F10
►
3 ~ 190 – 200 V
40 – 80 F10, F12, F14 ► 5 – 40 14
20 – 40 F10 ►
10 – 20 F07, F10
►
1 ~ 220 – 230 V
40 – 80 F10, F12, F14 ► 5 – 40 14
20 – 40 F10 ►
10
–
80
28
10 – 20 F07, F10
►
1 ~ 110 – 115 V
40 – 80 F10, F12, F14 ► 5 – 14 14
20 – 40 F10 ► 5 – 20 14
10 – 20 F07, F10
►