Operation instructions
SIPOS SEVEN: PROFITRON, HiMod
Page 74 Y070.302/EN
8 Parameters and possible parameter values
8.3 Parameters for the DCS
8
Parameters and possible parameter values
Range
4 – 20 mA
Detection of wire break is possible (live zero).
0 – 20 mA
Detection of wire break is not possible (dead zero).
Slope
Rising
4 mA corresponds to 0 % OPEN, 20 mA corresponds to 100 % OPEN.
Falling
4 mA corresponds to 100 % OPEN, 20 mA corresponds to 0 % OPEN.
8�3�11 Control system – Analog output AO2
Analog output AO2 is only displayed if the addi-
tional analog module is available. The setting of
the parameters is identical to 'Analog input AI1’,
refer to previous chapter.
8�3�12 Control system – Fieldbus
PROFIBUS DP
Only for available PROFIBUS interface.
For more detailed information, refer to PROFI-
BUS operation instructions.
PROFIBUS DP
Channel 1 address
Channel 2 address
PZD settings
Channel 1
Channel 1
Address 0 – 126
Fieldbus address of the actuator on channel
1 from 0 to 126.
Set to 126 in the factory.
Channel 2
Channel 2
Address 0 – 126
Channel 2 (redundant version only)
Fieldbus address of the actuator on channel 2 from 0 to 126.
Set to 126 in the factory.
Range
4 – 20 mA
0 – 20 mA
Slope
Rising
Falling
Address 0 – 126
Address 0 – 126
PZD 5 0 – XXX
PZD 3 0 – XXX
PZD 6 0 – XXX
PZD 4 0 – XXX
Channel 2
Channel 1
Process data
Control system
PROFIBUS DP
Fig�: ‘PROFIBUS DP‘ menu