Y070.302/EN Page 73
Operation instructions
SIPOS SEVEN: PROFITRON, HiMod
8
Parameters and possible parameter values
8 Parameters and possible parameter values
8�3 Parameters for the DCS
Warning motor temp�
The programmed motor warning
temperature has been exceeded (not for
2SG7…), refer to Page 85.
Fault external voltage
Low voltage or excessive voltage has been
detected, or power supply has failed.
Maintenance
One of the set maintenance limits has been
exceeded, refer to Page 86.
Run indication CLOSE
The actuator operates in CLOSE direction .
Run indication OPEN
The actuator operates in OPEN direction .
Run indication OPEN/CLOSE
The actuator runs in OPEN or CLOSE direc-
tion.
Blinker CL + end position CL
The actuator runs in CLOSE direction ; the
signal changes between ‚high‘ and ‘low‘ ev-
ery 2 sec. Once end position CLOSED has
been reached, the signal is set to ’active‘.
Alsorefertogureontheright.
Blinker OP + end position OP
The actuator runs in OPEN direction ; the
signal changes between ‚high‘ and ’low‘ ev-
ery 2 sec. Once end position CLOSED has
been reached, the signal is set to ’active‘.
‘End of travel CLOSE’ or ’End of travel
OPEN’
For limit dependant cut-off:
Signal is active if position 0% resp. 100%
is reached.
For torque dependant cut-off:
Signal is active if the respective end posi-
tion range is reached.
8�3�10 Control system – Analog output AO1
The analog output provides analog signals on:
The position of the actuator,
or
The actual process value for activated process
controller (transfers the sensor signal)
Process actual/position actual value
Process actual value
Actual process value is issued via the analog output. Only adjustable for process controller.
Position actual value
Actual position value is issued via the analog output.
Fig�: Blinker CL/OP parameter + end position signaling
Fig�: Parameter menu "Analog output AO1"
Slope
Analog output AO1
Process/position actual value
Range
Control system
Fieldbus
Position actual value
Process actual/position actual value
Process actual value
Default setting of signaling outputs
Signaling
output
Signal Level
1 End position OPEN NO
2 End position CLOSED NO
3 Torque OPEN reached NC
4 Torque CLOSE reached NC
5 Fault NC
6 Local NO
7 Blinker NO
8 Warning motor temp. NC
Fig�: Signalization End position OPEN/CLOSED