4 Instructions on operator control and operation
4
Instructions on operator control and operation
Status messages in the display including explanation
Signal Explanation Possible remedy
48 Fault AO2
No analog output via AO2 possible. Switch voltage on/off (AC/DC).
If the indication is still displayed, replace elec-
tronics unit.
49 No signal AO2
Connection between AO2 and DCS interrupted. Check feed cables or points of contact!
50 Fault hardware
Fault within the electronics. Switch voltage on/off (AC/DC).
If the indication is still displayed, replace elec-
tronics unit.
60 Fault Bluetooth
Communication fault in the Bluetooth module.
The actuator still is ready for operation and can be pro-
grammed using the local control station or COM-SIPOS.
Switch voltage on/off (AC/DC).
If the indication is still displayed, replace elec-
tronics unit.
61 Electronics temperature
Electronics temperature sensor defective.
The actuator is still ready for operation.
Switch voltage on/off (AC/DC).
If the indication is still displayed, replace elec-
tronics unit.
62 Fault position encoder
Bad signal quality of non-intrusive position encoder (niP);
position cannot be validated.
■
Check feed cables and contact points of
electronics/gear!
■
Check feed cables for separate installation.
63 No signal torque switch
Signals from both torque switches are not recognized.
■
Check feed cables and contact points of
electronics/gear!
■
Check feed cables for separate installation.
80 Warning RCU
No connection to the remote control unit.
■
Check feed cables or points of contact!
■
Verify parameterization of the remote control
unit at the actuator and at the remote control
unit.