4.5 Auto-Tuning
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 113
Start-Up Programming &
Operation
4
Auto-Tuning for Permanent Magnet Motors
Automatically sets the V/f pattern and motor parameters E1-, E5-, and some F1- parameters for speed
feedback detection.
Table 4.7 Types of Auto-Tuning for Permanent Magnet Motors
Table 4.8 lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting Auto-Tuning.
The information needed is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer. Also refer to Flowchart C: Auto-Tuning for PM Motors on page 110 for details on the tuning mode
selection and the tuning process.
Table 4.8 Auto-Tuning Input Data
Number of Motor Poles T1-06 YES YES N/A YES
Motor Rated Speed T1-07 r/min YES YES N/A YES
PG Number of Pulses per Revolution T1-08 YES
<1>
YES
<1>
N/A YES
<1>
Motor No-load Current T1-09 A N/A YES N/A YES
Motor Rated Slip T1-10 Hz N/A N/A N/A YES
<1> Input data is needed for CLV/PM only.
Type
<1> Available in drive software versions PRG: 7017 or later.
Auto-Tuning of PG-E3 encoder characteristics requires a PG-E3 option with software version 1102 or later. To identify the PG-E3 software
version, refer to the PG-E3 labeling on the option, in the field designated “C/N” (S + four digit number).
Setting Requirements and Benefits
Motor Data Input T2-01 = 0
Use if a motor test report is available.
Input motor data from the motor test report. Convert data into the correct unit before inputting data if necessary.
Motor does not rotate during Auto-Tuning.
Stationary Auto-Tuning T2-01 = 1
Use if a motor test report is not available.
Input motor data from the motor name plate. Make sure to convert data into the correct units. The drive automatically calculates the
motor data.
Stationary Stator Resistance
Auto-Tuning
T2-01 = 2
Tunes stator resistance only.
Should be performed if the motor cabling has changed.
Rotational Back EMF Constant
Auto-Tuning
T2-01 = 11
Use if a motor test is not available.
Tunes the Motor Induction Voltage only.
Should be performed after Motor data are set and the encoder offset is adjusted.
The motor must be uncoupled from the mechanical system (remove ropes).
Auto-Tuning of PG-E3 Encoder
Characteristics
<1>
T2-01 = 12 Perform this Auto-Tuning to obtain accurate position data from the motor rotor for driving a PM motor.
Input Value
Input
Parameter
Unit
Tuning Type (T2-01)
0
Motor
Parameter
Settings
1
Stationary
2
Stationary
Stator
Resistance
3
Initial
Magnet Pole
Search
Parameters
Auto-Tuning
4
Encoder
Offset
Stationary
Auto-Tuning
10
Encoder
Offset
Rotational
Auto-Tuning
11
Back EMF
Constant
12
Auto-
Tuning of
PG-E3
Encoder
Character-
istics
Control Mode A1-02 7 7 7 7 7 7 7 7
Motor Rated Power T2-04 kW Yes Yes N/A N/A N/A N/A N/A N/A
Motor Rated Voltage T2-05 V Yes Yes N/A N/A N/A N/A N/A N/A
Motor Rated Current T 2-0 6 A Yes Ye s Yes N /A N /A N /A N /A N/A
Number of Motor Poles T2-08 N/A Yes Yes N/A N/A N/A N/A N/A N/A
Motor Rated Speed T2-09 r/min Yes Yes N/A N/A N/A N/A N/A N/A
Stator 1 Phase Resistance T2-10
Ω
Yes N/A N/A N/A N/A N/A N/A N/A
d-Axis Inductance T2-11 mH Yes N/A N/A N/A N/A N/A N/A N/A
q-Axis Inductance T2-12 mH Yes N/A N/A N/A N/A N/A N/A N/A
Induced Voltage Constant Unit
Selection
T2-13 N/A Yes N/A N/A N/A N/A N/A N/A N/A
Voltage Constant T2-14
<2>
Yes N/A N/A N/A N/A N/A N/A N/A
PG Number of Pulses per
Revolution
T2-16 N/A Yes Yes N/A N/A N/A N/A N/A N/A
Z Pulse Offset T2-17 deg (mech.) Yes N/A N/A N/A N/A N/A N/A N/A
Input Value
Input
Parameter
Unit
Tuning Type (T1-01)
0
Standard
1
Stationary 1
2
Line-to-Line
Resistance
4
Stationary 2
Control Mode A1-02 2, 3 2, 3 0, 1, 2, 3 2, 3
SIEP_C710616_38F_5_0.book 113 ージ 015年11月9日 月曜日 午後3時36分