4.6 Setup Procedure for Elevator Applications
138 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Wiring for CIMR-LU20215 to 20415, 40150 to 40605, and 50099 to 50200
• Voltage Lower Than 48 to 190 Vdc for 200 V Class Drives, 48 to 380 Vdc for 400 V Class Drives, and 48 to 500 Vdc
for 600 V Class Drives
Figure 4. 18
Figure 4.23 Voltage Lower Than 48 to 190 Vdc for 200 V Class Drives, 48 to 380 Vdc for 400 V Class Drives,
and 48 to 500 Vdc for 600 V Class Drives
<1> Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than 190 Vdc for 200 V class drives
and 380 Vdc for 400 V class drives. Failure to comply will cause the soft-charge bypass relay to remain open and result in damage to the
drive.
+
Current
sensor
R/L1
S/L2
T/L3
+1
-
U/T1
V/T2
W/T3
Relay
Power
supply
board
Control
board
OPE
CN19
(A)
(C)
(B)
Battery for control circuit
200 V Class: 250 to 340 Vdc
400 V Class: 500 to 680 Vdc
600 V Class: 720 to 850 Vdc
DC bus
power supply
H1- = 55
(Rescue Operation)
L1
L2
L3
(D)
+3
Battery for DC bus
200 V Class: 48 to 190 Vdc
400 V Class: 48 to 380 Vdc
600 V Class: 48 to 500 Vdc
L1000A
After the DC bus voltage falls lower
than the battery voltage
0.5 s
After the DC bus voltage is charged
to the battery voltage
Magnetic Contactor B
Magnetic Contactor A
Magnetic Contactor C
Magnetic Contactor D
Magnetic Contactor Sequence
H1- = 55
(Rescue Operation)
S
3
to S
12
SC
Inrush current
suppression circuit
<1>
Inrush current suppression resistor
SIEP_C710616_38F_5_0.book 138 ページ 2015年11月9日 月曜日 午後3時36分