4.6 Setup Procedure for Elevator Applications
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 137
Start-Up Programming &
Operation
4
Using Separate Batteries for DC Bus and Control Power Supply, DC Bus Battery under 250
Vdc (500 Vdc, 720 Vdc)
Follow these instructions when using separate batteries for Rescue Operation with the battery for the DC bus having a
lower voltage than 250 Vdc for 200 V class drives, 500 Vdc for 400 V class drives, or 720 Vdc for 600 V class drives.
Follow the wiring diagram shown in Figure 4.22 to Figure 4.24. When connecting the battery for the control power
supply to the L1000A, use the 1.1 m cable packaged with the product. The connector cover must first be removed in order
to access connection port CN19 for the battery. Refer to Connecting the Drive and Battery on page 145 for details.
Wiring for CIMR-LU20008 to 20180, 40005 to 40112, and 50003 to 50077
Figure 4.17
Figure 4.22 Wiring Two Batteries for DC Bus and Control Power Supply
(DC Bus Battery is less than 250 Vdc (500 Vdc, 720 Vdc))
Operation Sequence
Starting Rescue Operation
1.
Open contactor B and wait at least 5 seconds.
2. Set the input terminal programmed for Rescue Operation (H1- = 55).
3. Close contactors A and C.
4. Set the Up/Down command.
Ending Rescue Operation
1.
After the car has stopped, open contactors A and C.
2. Clear the input terminal set for Rescue Operation (H1- = 55).
3. Wait at least 0.5 s and then close contactor B to return to operation with normal power supply.
-
Magnetic Contactor Sequence
L1000A
Control
circuit
Power s upply
Battery for DC bus
DC bus power supply
Battery for
control circuit
L1
L2
L3
CN19
1
4
W/T3
V/T2
U/T1
R/L1
S/L2
T/L3
B1
+2
+1
B2
SC
H1-غغ = 55
(Rescue Operation)
S3 to
S8
200 V Class: 48 to 250 Vdc
400 V Class: 48 to 500 Vdc
600 V Class: 48 to 720 Vdc
200 V Class: 250 to 340 Vdc
400 V Class: 500 to 680 Vdc
600 V Class: 720 to 850 Vdc
Magnetic Contactor A
Magnetic Contactor B
Magnetic Contactor C
H1-غغ = 55
(Rescue Operation)
Magnetic Contactor B
Magnetic Contactor A
Magnetic Contactor C
5 s
0.5 s
YEA_common