5.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 207
Parameter Details
5
Setting 53: Leveling speed
Closing a terminal set for “Leveling speed” makes the drive run at the speed reference set to d1-26. Conditions change,
however, according to the speed selection mode set in d1-18. Refer to Multi-Speed Inputs 1, 2 (d1-18 = 0 or 3) on
page 124 for details.
Setting 54: Inspection operation
Causes the drive to operate at the speed reference set in d1-24. To use Inspection Run, this terminal must be close before
the Up or Down command is entered. Refer to Inspection Operation on page 128 for details.
Setting 55: Rescue operation
Initiates Rescue Operation when the terminal closes. Refer to Rescue Operation on page 134 for details.
Setting 56: Motor contactor feedback
The drive monitors this input signal to detect malfunctions with the motor contactor. When the contactor is closed, the
terminal is closed. When the contactor is open, the terminal is open.
Setting 57: High speed limit up
When this input is closed the speed in the up direction will be limited to the leveling speed. No speed limit is applied
when the car is going down.
Setting 58: High speed limit down
When this input is closed the speed in the down direction will be limited to the leveling speed. No speed limit is applied
when the car is going up.
Setting 5A: Motor Contactor Feedback 2
The drive monitors this input signal to detect malfunctions with the motor contactor. When the contactor is closed, the
terminal is open. When the contactor is open, the terminal is closed.
Note: Setting 5A is available in drive software versions PRG: 7017 or later.
Setting 5B: Brake Feedback 2
The drive confirms brake operation with this input signal when a digital output is enabled (H2- = 50). When the brake
is activated, the terminal is closed. When the brake is not activated, the terminal is open.
Note: Setting 5B is available in drive software versions PRG: 7017 or later.
Setting 5C: Stop Distance Correction
When this terminal closes and a direct landing is selected for the stopping method (S5-10 = 1), the drive will stop at the
designated floor with greater accuracy. Refer to Stop Distance on page 427 for details.
Setting 67: Communication test mode
The drive has a built-in function for self-diagnosing serial communications operation. The test involves wiring the send
and receive terminals of the RS-485/422 port together. The drive transmits data and then confirms that the
communications are received normally. Refer to Self-Diagnostics on page 470 for details on how to use this function.
Setting 79: Brake feedback
This input allows the drive to monitor the brake operation and issue a fault if the brake status does not match the brake
command (digital output set to H2- = 50).