to 50041)
■ L8-77: Oscillation Suppression
If speed oscillations with the same frequency as the output frequency occur with an unloaded motor, parameter L8-77 can
be adjusted to suppress these oscillations. While watching the motor speed, increase or decrease L8-77 until the
oscillation disappears.
This parameter rarely requires adjustment.
■
L8-88: Safe Disable Operation Mode
Determines the operation performed by the drive when the Safe Disable input is activated.
Setting 0: Mode 0
Setting 1: Mode 1
When the Safe Disabled Input is triggered, the operator displays and alarm, and the corresponding output terminal will
react as follows.
No. Parameter Name Setting Range Default
L8-77 Oscillation Suppression –100 to 100 0
No. Parameter Name Setting Range Default
L8-88 Safe Disable Operation Mode 0 or 1 1
L8-88
Safe Disable Operation
Selection
Alarm Display during Safety Disable Alarm Output (H2- = 10)
Drive Ready
(H2- = 6)
0 (mode 0) Hbb ALM flashes ON OFF
1 (mode1) Hbb ALM flashes OFF ON