5.8 L: Protection Functions
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 241
■ L8-89: Current Monitoring Selection
Note: Available in drive software PRG: 7017 or later.
Enables or disables the Current Monitoring function. When this parameter is set to 1 (Enabled), the current monitoring
level (L8-99) is added to the conditions required to turn off the Motor Contactor Feedback command at a stop.
Setting 0: Disabled
Setting 1: Enabled
■ L8-99: Current Monitoring Level
Note: Available in drive software PRG: 7017 or later.
Sets the current monitoring level as a percentage of the drive’s rated current. When the output current is equal to or below
the set level, the Motor Contactor Feedback command turns off if the current monitoring selection is enabled (L8-89 = 1).
This parameter is also used to activate the Motor Current Monitor (H2- = 5C).
No. Parameter Name Setting Range Default
L8-89 Current Monitoring Selection 0, 1 0
No. Parameter Name Setting Range Default
L8-99 Current Monitoring Level 0.0 to 50.0% 10.0%