5.11 S: Elevator Parameters
266 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
S4-12: DC Bus Voltage during Rescue Operation
Sets the DC bus voltage during Rescue Operation.
S4-13: Rescue Operation Power Supply Deterioration Detection Level
Determines at which level of backup power supply deterioration a PF5 fault is triggered. The following conditions will
trigger PF5:
During Rescue Operation, DC bus voltage < [S4-12 × (S4-13 – 10%)]
100 ms after Rescue Operation has been triggered, the DC bus voltage does not rise above S4-12 × S4-13 before the
motor starts
S4-15: Speed Reference Selection at Rescue Operation
Note: Available in drive software PRG: 7016 or later.
Selects the speed reference used for Rescue Operation.
Setting 0: The setting of parameter d1-25 is used as speed reference for Rescue Operation
Setting 1: The speed selected by digital inputs is used as speed reference
No. Parameter Name Setting Range Default
S4-12 DC Bus Voltage during Rescue Operation 0 to 1150 V 0 V
No. Parameter Name Setting Range Default
S4-13 Rescue Operation Power Supply Deterioration Detection Level 10 to 100% 80%
No. Parameter Name Setting Range Default
S4-15 Speed Reference Selection for Rescue Operation 0, 1 0
SIEP_C710616_38F_5_0.book 266 ージ 015年11月9日 月曜日 午後3時36分