7.4 Drive Cooling Fans and Circulation Fans
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 335
Periodic Inspection &
Maintenance
7
4. Remove the fan guard and replace the cooling fans.
Note: Do not pinch the fan cable between parts when reassembling the fan unit.
Figure 7.21
Figure 7.21 Fan Unit Disassembly: 20145 to 20415, 40112 to 40304, and 50052 to 50200
■ Cooling Fan Wiring: CIMR-LU20145, 20180, 40112, 40150, and 50052 to 50077
1. Position the protective tube so that the fan connector sits in the center of the protective tube.
2. Place the fan connector covered by the tube as shown in Figure 7.22.
Figure 7.22
Figure 7.22 Cooling Fan Wiring for Models 20145, 20180, 40112, 40150, and 50052 to 50077
A – Fan guard C – Cooling Fan
B – Cable Cover D – Circulation Fan
C
A
A
C
D
B
B
40216 to 40260
20346, 20415
40304
50172, 50200
A
C
20145 to 20283
40112 to 40180
50052 to 50130
20145, 20180, 40112,
50052 to 50077
40150
Connector for fan B1
Fan B1
Fan B2
Connector for fan B2