A.5 Drive Watt Loss Data
384 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Table A.6 Watt Loss 600 V Class Three-Phase Models
Model Number
CIMR-LU
<1> These values assume the carrier frequency is set to 8 kHz or less.
<2> These values assume the carrier frequency is set to 5 kHz or less.
<3> These values assume the carrier frequency is set to 3 kHz or less.
Carrier Frequency 8 kHz
Rated Amps (A) Heatsink Loss (W) Interior Unit Loss (W) Total Loss (W)
50003 3.5
<1>
54.3 27.6 81.9
50004 4.1
<1>
53.0 27.0 80.0
50006 6.3
<1>
78.7 36.4 115.1
50010 9.8
<1>
110.9 49.5 160.3
50013 12.5
<1>
144.7 67.5 212.2
50017 17
<1>
203.8 81.1 284.8
50022 22
<1>
267.2 113.8 381.1
50027 27
<1>
332.9 132.2 465.1
50032 32
<1>
405.9 127.6 533.5
50041 41
<1>
527.2 161.4 688.5
50052 52
<1>
1271.5 355.0 1606.5
50062 62
<1>
1457.0 379.5 1836.5
50077 77
<2>
1267.0 352.0 1619.0
50099 99
<3>
1328.0 422.0 1750.0
50130 130
<3>
1638.0 508.0 2146.0
50172 172
<3>
2114.0 648.0 2762.0
50200 200
<3>
2526.0 896.0 3422.0