B.3 Parameter Table
432 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
■ U2: Fault Trace
U1-16
(53H)
Output Speed after Soft Start
Displays output speed with ramp time and jerk settings. Units determined by o1-03.
10 V: Max frequency
(-10 to +10 V)
0.01%
<29>
–
U1-17
(58H)
DI-A3 Option Card Input
Status
Displays the reference value input from the DI-A3 option card.
Display will appear in hexadecimal as determined by the digital card input selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bit
No signal output
available
––
U1-18
(61H)
oPE Fault Parameter
Displays the parameter number that caused the oPE02 or oPE08 (Operation error).
No signal output
available
––
U1-19
(66H)
MEMOBUS/Modbus Error
Code
Displays the contents of a MEMOBUS/Modbus error.
No signal output
available
––
U1-25
(4DH)
Software Number (Flash)
FLASH ID
No signal output
available
––
U1-26
(5BH)
Software No. (ROM)
ROM ID
No signal output
available
––
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU20008 to 20033, 40005 to 40018, and
50003 to 50013 display values in 0.01 A units, while models CIMR-LU20047 to 20415, 40024 to 40605, and 50017 to
50200 display values in 0.1 A units.
<12> The display resolution depends on the rated output power of the drive. Models CIMR-LU20008 to 20033, 40005 to 40018, and
50003 to 50013 display values in 0.01 kW units, while models CIMR-LU20047 to 20415, 40024 to 40605, and 50017 to
50200 display values in 0.1 kW units.
<29> Setting units are determined by the digital operator display unit selection (o1-03). When o1-03 = 0, the value is set in Hertz. When o1-03 = 4
or 5, the value is displayed in m/s. When o1-03 = 6, the value is displayed in ft/min.
<40> When checking the values of U1-03, U2-05 and U4-13 with the digital operator they are displayed in units of amperes, but when they are
checked using MEMOBUS communications, the monitor value in MEMOBUS communications is: displayed numeric value / 8192 × drive’s
rated current (A), from the condition “8192 (maximum value) = drive’s rated current (A)”.
No. (Addr.) Name Description
Analog Output
Level
Unit Page
U2-01
(80H)
Current Fault
Displays the current fault.
No signal output
available
––
U2-02
(81H)
Previous Fault
Displays the previous fault.
No signal output
available
––
U2-03
(82H)
Speed Reference at Previous
Fault
Displays the speed reference at the previous fault.
No signal output
available
0.01%
<29>
–
U2-04
(83H)
Output Speed at Previous Fault
Displays the output speed at the previous fault.
No signal output
available
0.01%
<29>
–
U2-05
(84H)
Output Current at Previous
Fault
Displays the output current at the previous fault.
No signal output
available
<10> <40>
–
U2-06
(85H)
Motor Speed at Previous Fault
Displays the motor speed at the previous fault.
No signal output
available
0.01%
<29>
–
U2-07
(86H)
Output Voltage at Previous
Fault
Displays the output voltage at the previous fault.
No signal output
available
0.1 Vac –
No. (Addr.) Name Description
Analog Output
Level
Unit Page
All Modes
All Modes
All Modes
All Modes
U1
-
19=00000000
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes