EasyManua.ls Logo

YASKAWA L1000A - Page 483

YASKAWA L1000A
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D.3 UL and CSA Standards
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 483
Standards Compliance
D
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C (167°F) 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed
40°C (104°F).
Table D.5 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
20215
<2>
R/L1, S/L2, T/L3 3/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
–, +1 3/0 to 300
+3 2 to 300 M10
18 to 23
(159 to 204)
33 to 300M12
32 to 40
(283 to 354)
20283
<2>
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
–, +1 3/0 to 300
+3 3/0 to 300 M10
18 to 23
(159 to 204)
22 to 300M12
32 to 40
(283 to 354)
20346
<2>
R/L1, S/L2, T/L3 250 × 2P 4/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 2P 4/0 to 600
–, +1 250 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
11 to 350M12
32 to 40
(283 to 354)
20415
<2>
R/L1, S/L2, T/L3 350 × 2P 250 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 2P 300 to 600
–, +1 300 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
11 to 350M12
32 to 40
(283 to 354)
<1> When an EMC filter is installed, additional measures must be taken in order to comply with IEC/EN 61800-5-1. Refer to EMC Filter
Installation on page 477.
<2> Drive models CIMR-LU20085 to 20415 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Model
CIMR-LU
Terminal
Recommended Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
40005
40006
40007
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 14 to 10
B1, B2 14 to 10
10 14 to 10
40009
R/L1, S/L2, T/L3 12 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 14 to 10
B1, B2 14 to 10
10 14 to 10
40015
R/L1, S/L2, T/L3 10 12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3 10 12 to 6
–, +1, +2 12 to 6
B1, B2 12 to 10
10 14 to 10 M5
2.0 to 2.5
(17.7 to 22.1)
40018
R/L1, S/L2, T/L3 10 10 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3 10 10 to 6
–, +1, +2 12 to 6
B1, B2 12 to 10
10 12 to 10 M5
2.0 to 2.5
(17.7 to 22.1)
Model
CIMR-LU
Terminal
Recommended Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
SIEP_C710616_38F_5_0.book 483 ージ 015年11月9日 月曜日 午後3時36分