D.3 UL and CSA Standards
484 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
40024
R/L1, S/L2, T/L3 8 8 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3 8 10 to 6
–, +1, +2 – 10 to 6
B1, B2 – 10 to 8 M5
2.7 to 3.0
(23.9 to 26.6)
810 to 8M6
5.4 to 6.0
(47.8 to 53.1)
40031
R/L1, S/L2, T/L3 6 8 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3 8 8 to 6
–, +1, +2 – 6
B1, B2 – 10 to 8 M5
2.7 to 3.0
(23.9 to 26.6)
610 to 6M6
5.4 to 6.0
(47.8 to 53.1)
40039
R/L1, S/L2, T/L3 6 6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3 6 6 to 4
–, +1, +2 – 6 to 4
B1, B2 – 10 to 8 M5
2.7 to 3.0
(23.9 to 26.6)
68 to 6M6
5.4 to 6.0
(47.8 to 53.1)
40045
<1>
R/L1, S/L2, T/L3 4 6 to 4
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 4 6 to 4
–, +1 – 6 to 1
B1, B2 – 8 to 4
68 to 6
40060
<1>
R/L1, S/L2, T/L3 3 4 to 3
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 3 4 to 3
–, +1 – 4 to 1
B1, B2 – 6 to 3
66
40075
<1>
R/L1, S/L2, T/L3 2 3 to 1/0
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 2 3 to 1/0
–, +1 – 3 to 1/0
+3 – 6 to 1/0
46 to 4
40091
<1>
R/L1, S/L2, T/L3 1/0 2 to 1/0
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 1 2 to 1/0
–, +1 – 3 to 1/0
+3 – 4 to 1/0
46 to 4
40112
<1>
R/L1, S/L2, T/L3 3/0 1/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 2/0 1/0 to 4/0
–, +1 – 1/0 to 4/0
+3 – 3 to 4/0
44
40150
<1>
R/L1, S/L2, T/L3 4/0 3/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 4/0 3/0 to 4/0
–, +1 – 1 to 4/0
+3 – 1/0 to 4/0
44 to 2
40180
<1>
R/L1, S/L2, T/L3 300 2 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 300 2 to 300
–, +1 – 1 to 250
+3 – 3 to 3/0
44 to 300
40216
<1>
R/L1, S/L2, T/L3 400 1 to 600
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 400 1/0 to 600
–, +1 – 3/0 to 600
+3 – 1 to 325
22 to 350
Model
CIMR-LU
Terminal
Recommended Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
SIEP_C710616_38F_5_0.book 484 ページ 2015年11月9日 月曜日 午後3時36分