3.8 Control Circuit Wiring
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 79
■ Output Terminals
WARNING! Sudden Movement Hazard. The logic of terminals DM+/DM- is inverted between drive models CIMR-LA and
CIMR-LF. Check all wiring to ensure that the sequence is correct after installing the drive and connecting any other devices.
Improper wiring connections could result in death or serious injury.
Table 3.7 lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
output.
Note: Multi-function relay output terminals are rated at a minimum of 10 mA. If less than 10 mA is required, use the photocoupler
outputs (P1-C1, P2-C2). Using the wrong current output level may cause the output to malfunction when the terminal is activated.
Table 3.7 Control Circuit Output Terminals
Figure 3.18
Figure 3.19 Connecting a Suppression Diode
Analog Inputs
+V
Power supply for analog inputs 10.5 Vdc (max allowable current 20 mA) 166
-V
Power supply for analog inputs -10.5 Vdc (max allowable current 20 mA) –
A1
Multi-function analog input 1 (Speed reference bias) -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
166
217
A2
Multi-function analog input 2 (Not used) -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
166
218
AC
Analog input common 0 V 166
E (G)
Ground for shielded lines and option cards – –
<1> Setting jumper S3 for an external power supply makes the wire jumper between terminals H1, H2, and HC ineffective. Remove the wire jumper
and connect an external power supply that can supply terminals H1, H2, and HC continuously.
<2> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Type
<1> Refrain from assigning functions to terminals M1 thru M6 that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Connect a suppression diode as shown in Figure 3.19 when driving a reactive load such as a relay coil. Make sure the diode rating is greater
than the circuit voltage.
<3> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
No. Terminal Name (Function) Function (Signal Level) Default Setting Page
Fault Relay
MA
N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
208
MB
N.C. output
MC
Fault output common
Multi-Function
Relay Output
<1>
M1
Multi-function relay output 1 (Brake release command)
Contact relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
208
M2
M3
Multi-function relay output 2 (Output contactor close command)
M4
M5
Multi-function relay output 3 (Drive ready)
M6
Multi-Function
Photocoupler
Output
P1
Photocoupler output 1 (During Frequency output)
48 Vdc, 2 to 50 mA
<2>
–
C1
P2
Photocoupler output 2 (Not Used/Through Mode)
C2
Monitor Output
FM
Analog monitor output 1 (Output speed)
-10 to +10 Vdc or 0 to +10 Vdc 220
AM
Analog monitor output 2 (Output current)
AC
Monitor common 0 V –
Safety Monitor
Output
<3>
DM+
Safety monitor output
Outputs status of Safe Disable function. Up to +48 Vdc 50 mA 496
DM-
Safety monitor output common
A – External power, 48 V max. C – Coil
B – Suppression diode D – 50 mA or less
Type No. Terminal Name (Function) Function (Signal Level) Default Setting Page
B
C
D
SIEP_C710616_38F_5_0.book 79 ページ 2015年11月9日 月曜日 午後3時36分