Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
4Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Abs high
5Action is taken whenever the signal falls below its low limit
or rises above its high limit.
Both
6Action is taken whenever the absolute value of the signal
falls below its (absolute) low limit or rises above its
(absolute) high limit.
Abs both
No action / uint16Selects the action the drive takes when the value monitored
by signal supervision 3 exceeds its limits.
Note: This parameter does not affect the status indicated
by 32.1 Supervision status.
Supervision 3 action32.26
0No action taken.No action
1
A warning (A8B2 Signal supervision 3) is generated.
Warning
2
The drive trips on 80B2 Signal supervision 3.
Fault
3
If running, the drive trips on 80B2 Signal supervision 3.
Fault if running
Zero / uint32Selects the signal to be monitored by signal supervision
function 3.
For the available selections, see parameter 32.7
Supervision 1 signal.
Supervision 3 signal32.27
0.000 s / real32Defines a filter time constant for the signal monitored by
signal supervision 3.
Supervision 3 filter
time
32.28
1000 = 1 s / 1000 = 1
s
Signal filter time.0.000 ... 30.000 s
0.00 / real32Defines the lower limit for signal supervision 3.Supervision 3 low32.29
- / -Low limit.-21474830.00 ...
21474830.00
0.00 / real32Defines the upper limit for signal supervision 3.Supervision 3 high32.30
- / -Upper limit.-21474830.00 ...
21474830.00
344 Parameters