What to doCause
Event name /
Aux. code
Code
(hex)
AI1 over maximum, 03: AI2 under
minimum, 04: AI2 over maximum).
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group 12
Standard AI, 14 I/O extension module 1,
15 I/O extension module 2 or 16 I/O
extension module 3.
Check the source of the warning
(parameter 32.7 Supervision 1 signal).
Warning generated by the signal
supervision 1 function.
Signal
supervision
A8B0
Check the source of the warning
(parameter 32.17 Supervision 2 signal).
Warning generated by the signal
supervision 2 function.
Signal
supervision 2
A8B1
Check the source of the warning
(parameter 32.27 Supervision 3 signal).
Warning generated by the signal
supervision 3 function.
Signal
supervision 3
A8B2
Check for any operating conditions
increasing the monitored signal (for
Selected signal has exceeded the user
overload curve.
ULC overloadA8BE
example, the loading of the motor if the
torque or current is being monitored).
Check the definition of the load curve
(parameter group 37 User load curve).
Check for any operating conditions
decreasing the monitored signal (for
Selected signal has fallen below the user
underload curve.
ULC underloadA8BF
example, loss of load if the torque or
current is being monitored).
Check the definition of the load curve
(parameter group 37 User load curve).
Check the auxiliary code. The code
indicates which fan is to be replaced.
A cooling fan has reached the end of its
estimated lifetime.
Fan service
counter
A8C0
0: Main cooling fan
See parameters 5.41 and 5.42.
1: Auxiliary cooling fan
2: Auxiliary cooling fan 2
3: Cabinet cooling fan
4: PCB compartment fan
Refer to the hardware manual of the
drive for fan replacement instructions.
Check the external device.Fault in external device 1.External
warning 1
A981
Check setting of parameter 31.1 External
event 1 source.
Check the external device.Fault in external device 2.External
warning 2
A982
Check setting of parameter 31.3 External
event 2 source.
Check the external device.Fault in external device 3.External
warning 3
A983
Check setting of parameter 31.5 External
event 3 source.
Check the external device.Fault in external device 4.External
warning 4
A984
Check setting of parameter 31.7 External
event 4 source.
Check the external device.Fault in external device 5.External
warning 5
A985
Check setting of parameter 31.9 External
event 5 source.
Fault tracing 575