Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint32Defines a start delay for the motor fan.
The delay timer starts when the control source selected
by parameter 35.100 switches on. After the delay, bit 1 of
35.105 switches on.
DOL starter on delay35.101
1 = 1 s / 100 = 1 sMotor fan start delay.0...42949673 s
20 min / uint32Defines a stop delay for the motor fan.
The delay timer starts when the control source selected
by parameter 35.100 switches off. After the delay, bit 1 of
35.105 switches off.
DOL starter off delay35.102
1 = 1 min / 1 = 1 minMotor fan stop delay.0...715828 min
Not selected; DI5
(95.20 b6) / uint32
Selects the input for motor fan feedback signal.
0 = Stopped
1 = Running
After the fan is started (bit 1 of 35.105 switches on),
feedback is expected within the time set by 35.104.
DOL starter feedback
source
35.103
00Not selected
11Selected
2
Digital input DI1 (10.2 DI delayed status, bit 0).
DI1
3
Digital input DI2 (10.2 DI delayed status, bit 1).
DI2
4
Digital input DI3 (10.2 DI delayed status, bit 2).
DI3
5
Digital input DI4 (10.2 DI delayed status, bit 3).
DI4
6
Digital input DI5 (10.2 DI delayed status, bit 4).
DI5
7
Digital input DI6 (10.2 DI delayed status, bit 5).
DI6
10
Digital input/output DIO1 (11.2 DIO delayed status, bit 0).
DIO1
11
Digital input/output DIO2 (11.2 DIO delayed status, bit 1).
DIO2
Source selection See Terms and abbreviations (page 132).
Other [bit]
0; 5 (95.20 b6) s /
uint32
Defines a feedback delay for the motor fan.
The delay timer starts when bit 1 of 35.105 switches on. If
no feedback is received from the fan until the delay
elapses, the action selected by 35.106 is taken.
Note: This delay is only applied at start. If the feedback
signal is lost during run, the action selected by 35.106 is
taken immediately.
DOL starter feedback
delay
35.104
1 = 1 s / 1 = 1 sMotor fan start delay.0...42949673 s
- / uint16Status of the motor fan control logic.
Bit 1 is the control output for the fan, to be selected as the
source of, for example, a digital or relay output.
The other bits indicate the statuses of the selected control
and feedback sources, and the fault status.
This parameter is read-only.
DOL starter status
word
35.105
Status of fan control source selected by 35.100.
0 = Stop requested
1 = Start requested
Start command:b0
Parameters 365