Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / real32
Defines process setpoint preset 2. See parameter 40.19
Set 1 internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit
selection.
Set 1 internal setpoint
2
40.22
1 = 1 / 100 = 1Process setpoint preset 2.-32768.00 ...
32767.00
- / real32
Defines process setpoint preset 3. See parameter 40.19
Set 1 internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit
selection.
Set 1 internal setpoint
3
40.23
1 = 1 / 100 = 1Process setpoint preset 3.-32768.00 ...
32767.00
- / real32
Defines process setpoint preset 4. See parameter 40.19
Set 1 internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit
selection.
Set 1 internal setpoint
4
40.24
1 = 1 / 100 = 1Process setpoint preset 4.-32768.00 ...
32767.00
Setpoint source 1 /
uint32
Configures the selection between setpoint sources 1
(40.16) and 2 (40.17).
This parameter is only effective when parameter 40.18 Set
1 setpoint function is set to In1 or In2.
0 = Setpoint source 1
1 = Setpoint source 2
Set 1 setpoint
selection
40.25
00.Setpoint source 1
11.Setpoint source 2
2
Digital input DI1 (10.2 DI delayed status, bit 0).
DI1
3
Digital input DI2 (10.2 DI delayed status, bit 1).
DI2
4
Digital input DI3 (10.2 DI delayed status, bit 2).
DI3
5
Digital input DI4 (10.2 DI delayed status, bit 3).
DI4
6
Digital input DI5 (10.2 DI delayed status, bit 4).
DI5
7
Digital input DI6 (10.2 DI delayed status, bit 5).
DI6
10
Digital input/output DIO1 (11.2 DIO delayed status, bit 0).
DIO1
11
Digital input/output DIO2 (11.2 DIO delayed status, bit 1).
DIO2
See Terms and abbreviations (page 132).
Other [bit]
0.00 / real32Defines a minimum limit for the process PID controller
setpoint.
Set 1 setpoint min40.26
1 = 1 / 100 = 1Minimum limit for process PID controller setpoint.-32768.00 ...
32767.00
32767.00 / real32Defines a maximum limit for the process PID controller
setpoint.
Set 1 setpoint max40.27
1 = 1 / 100 = 1Maximum limit for process PID controller setpoint.-32768.00 ...
32767.00
380 Parameters