Connecting inputs
53
1SVC 440 795 M1100
AC expansion device CL-LER.18AC2
Figure: 35: Inputs on the CL-LER.18AC2 expansion device
Connect the inputs, for example, to pushbutton actuators,
switches or relay/contactor contacts.
Input signal voltage range
Off signal: 0 to 40 V
On signal: 79 to 264 V
Input current
I1 to I12 0.5 mA/0.2 mA at 230 V/115 V
R1 to R12 0.5 mA/0.25 mA at 230 V/115 V
Cable lengths
Severe interference can cause a signal 1 on the inputs
without a proper signal being applied. Observe therefore the
following maximum cable lengths:
•I1 to I2 and
R1 to R12: 40 m without additional circuit
L1
N
R10R9R8R7R6R5R4R3R2R1E+ E–
R11
R12 NNL
115/230 V h