15.10.2.2 Keypads
Editing a Standard Keypad
1. Select Configuration > Hardware > X-Bus > Keypads.
2. Click one of the standard keypad identifying parameters.
3. Configure the fields as described in the table below.
Description Enter a unique description to identify the keypad.
Function Keys (in idle state)
Panic Select Enable, Disable or Enabled Silent. If enabled, panic alarm is activated
by pressing the 2 soft keys together.
Verification If you assign a verification zone to the keypad, when a panic alarm is
triggered by pressing 2 soft keys together or by entering a duress code, audio
and video events are activated.
Visual Indications
Backlight Select when keypad backlight is on. Options are: On after key is pressed;
Always on; Always off.
Indicators Enable or disable the LED’s on the keypad.
Setting state Select if setting state should be indicated in idle mode.
Audible Indications
Buzzer Enable or disable the buzzer on the keypad.
Partset
Buzzer
Enable or disable buzzer during exit time on Partset.
Keypress Select if the speaker volume for the key presses should be activated.
Deactivation
Calendar Select if the keypad should be limited by calendar. See Calendars on
page197.
Mapping gate Select if keypad should be limited by a mapping gate.
Keyswitch Select if keypad should be limited by a keyswitch.
PACE Entry Tick this box to disable the keys on the keypad during the entry time when a
PACE is configured on the keypad.
Areas
Location Select the secured area where the keypad is located.
Areas Select which areas can be controlled through keypad.
Options
Delay Fullset Select to configure a delayed set across all keypads. The location of the
keypad is ignored and all areas will perform a full exit time count down.
SPC42/52/53/63 – Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2023 165 I-200572
08.12.2023