Restriction System Option Description
Out of bounds
EOL set
Select the type of event reported resulting from Out of Bounds EOL
detection when the panel is set. Options are: Disabled, Tamper and Trouble.
The option can only be configured when the panel is in ‘Unrestricted’ mode.
In Grade 2 or 3 mode, the type of event reported is in accordance with the
standards for the selected region:
l
Germany VDS Tamper
l
All other regions Trouble
Zone Unstable
unset
Select the type of event reported resulting from Zone Unstable detection
when the panel is unset. Options are: Disabled, Tamper and Trouble.
A zone is unstable if a valid sample cannot be obtained within 10 seconds.
The option can only be configured when the panel is in ‘Unrestricted’ mode.
In Grade 2 or 3 mode, the type of event reported is in accordance with the
standards for the selected region:
l
Germany VDS Tamper
l
All other regions Trouble
Zone Unstable
set
Select the type of event reported resulting from Zone Unstable detection
when the panel is set. Options are: Disabled, Tamper and Trouble.
A zone is unstable if a valid sample cannot be obtained within 10 seconds.
The option can only be configured when the panel is in ‘Unrestricted’ mode.
In Grade 2 or 3 mode, the type of event reported is in accordance with the
standards for the selected region:
l
Germany VDS Tamper
l
All other regions Trouble
End Of Line
(EOL
RESISTANCE)
Select the End Of Line termination resistors that will apply to either all zones
on the system or new zones added to the system. Select a value to enable
the appropriate feature.
To apply a new EOL setting to all existing zones, select the Update all zones
checkbox. If you change the End of Line value but do not select this
checkbox, the new setting applies only to zones added after changing the
value.
EOL Wide If enabled, EOL wide bands are used.
Suspicion
Audible
If enabled then WPA* Suspicion alerts have audible and visible indicators on
the keypad (Financial mode only).
Seismic Test on
Set
If enabled, all seismic sensors in any area that is being set will be tested
before area or system set (Financial mode only).
Auto Restore Enable this feature to automatically restore alerts on the system, that is,
when the open zone that triggered an alarm is closed, a manual restore
operation on the keypad/browser is not required. If disabled it prevents the
user from restoring alerts by resetting the input that triggered the alert.
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the browser