Restriction System Option Description
Alarm on Exit Enabled: If a non-entry/exit zone is activated during the exit timer
countdown, a local alarm is raised by sounding the bells.
Disabled: If a non-entry/exit zone is activated during the exit timer
countdown, an alarm is not raised.
Note: This option only displays when the Unrestricted grade is selected as
enabling it is not in accordance with EN50131. When you choose the Swiss
or Belgium Region under Standard Compliance Settings, this option is
automatically enabled but it is not visible under Options.
Alarm on Entry Enabled: If a non-entry/exit zone is activated during the entry timer
countdown, a local alarm is raised by sounding the bells.
Disabled: If a non-entry/exit zone is activated during the entry timer
countdown, an alarm is not raised.
Note: This option only displays when the Unrestricted grade is selected as
enabling it is not in accordance with EN50131. When you choose the Swiss
Region under Standard Compliance Settings, this option is automatically
enabled but it is not visible under Options.
Confirmation
Confirmation The Confirmation variable determines when an alarm is deemed to be a
confirmed alarm.
l
BS8243:
This will enforce compliance with the UK Police requirements, and is a
specific requirement for UK Commercial installations. The requirement
stipulates that an alarm will only be deemed to be a confirmed alarm if it
meets the following condition:
After an initial zone alarm has been activated and before the alarm
confirmation time has expired, a second zone alarm is activated. The
alarm confirmation time must be between 30 and 60 minutes. (See
Timers on page179.)
If a second zone alarm is not activated within the Alarm confirmation
time, then the first zone alarm will be inhibited. The BS8243 confirmation
option is automatically set whenever the Standards > Region option is
set to UK.
l
Garda:
This will enforce the policies for confirmed alarms required by the Irish
Garda. The requirement stipulates that an alarm will be deemed to be a
confirmed alarm as soon as a second zone alarm is activated on the
system within the one alarm set period. The Garda confirmation option
is automatically set whenever the Standards > Region option is set to
Ireland.
l
EN-50131-9
This will enforce compliance with the EN-50131-9 standard and the
Spanish “INT/316/2011 Order of 1 February on the operation of alarm
systems in the field of private security”. This requirement stipulates that
an alarm will only be deemed to be a confirmed alarm if it meets the
following conditions:
- 3 zone activations in 30 minutes (default), whereby two activations
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the browser