Timer Description Default
Setting
Setting Authorisation
SETTING AUTH
Period for which Setting Authorisation is valid. (10–250
seconds)
10 sec
Final Exit
FINAL EXIT
The Final Exit time is the number of seconds that arming is
delayed after a zone programmed with the final exit attribute
is closed. (1–45 seconds)
7 sec.
Bell on Fullset
FULLSET BELL
Activates the external bell momentarily to indicate a full set
condition. (0–10 seconds)
0 sec.
Fail To Set
FAIL TO SET
Number of seconds to display fail to set message on
keypads (0 until valid PIN is entered). (0–999 seconds)
10 sec.
Strobe on Fullset
FULLSET STROBE
Activates the strobe on the external bell momentarily to
indicate a full set condition. (0–10 seconds)
0 sec.
DELAYUNSETBUZZERTIME 1 sec
Alarm
Double Knock
DKNOCK DELAY
The maximum delay between activation’s of zones with the
double attribute, which will cause an alarm. (1–99 seconds)
10sec.
Soak
SOAK DAYS
The number of days a zone remains under soak test before it
automatically returns to normal operation. (1–99 days)
14 days
Seismic Test Interval
SEISMIC AUTOTEST
The average period between seismic sensor automatic
tests. (12–240 hours)
Note: To enable automatic testing, the Automatic Sensor
Test attribute must be enabled for a seismic zone.
168 hours
Seismic Test Duration
SEISMIC TEST DUR
Maximum time (in seconds) that a seismic sensor takes to
trigger an alarm in response to the 'Seismic Test' output. (3–
120 seconds)
30 sec.
Auto Restore Delay Time to delay auto restore after zone state returns to normal.
(0–9999 seconds)
0 sec.
Lockout Post Alarm
LOCKOUT POST ALARM
The duration of time after an alarm before the user can gain
access. (1–120 minutes)
30 min.
Access Time The duration of time the system can be accessed by an
alarm access user after the Lockout Time has elapsed. (10–
240 minutes)
120 min
External Bell Strobe
STROBE TIME
Duration that the strobe output will be active when an alarm
is activated. (1–999 minutes; 0=indefinitely)
15min.
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2023 181 I-200572