Timer Description Default
Alerts
Mains Delay
MAINS SIG DELAY
The time after a mains fault has been detected before an
alert is activated by the system. (0–60 minutes)
0min.
RFJamming Delay The time after RF Jamming has been detected before an
alert is activated by the system. (0–999 seconds)
0min.
Engineer
Engineer Access
ENGINEER ACCESS
The timer for the Engineer access starts as soon as the user
enables the Engineer Access. (0–999 minutes; 0 indicates
no time limitation for system access)
0 min.
Engineer auto log out
ENG AUTO LOG OUT
Duration of inactivity after which the engineer will be
automatically logged out. (0–300 minutes)
0 min.
Keypad
Keypad Timeout
KEYPAD TIMEOUT
The number of seconds that an RKD will wait for key entry
before it leaves the current menu. (10–300 seconds)
30 sec.
Keypad Language
KEYPAD LANGUAGE
The duration a keypad will wait in idle before switching
language to default. (0–9999 seconds; 0=never)
10 sec.
CODELOCKOUT 10 sec
CODE LOCKOUT 2 10 sec
Lockout time 90 sec
Fire
Fire Pre-alarm
FIRE PRE-ALARM
Number of seconds to wait before reporting fire alarm for
zones with ‘Fire pre-alarm’ attribute set. See Editing a zone
on page185. (1–999 seconds)
30sec.
Fire recognition
FIRE RECOGNITION
Extra time to wait before reporting file alarm for zones with
‘Fire pre-alarm’ and ‘Fire Recognition’ attributes set. See
Editing a zone on page185. (1–999 seconds)
120sec.
PIN
PIN Valid
PIN VALID
Period for which pin is valid. (1–330 days) 30 days
PIN Changes Limit
PIN CHANGES LIMIT
Number of changes within a valid period. (1–50) 5
PIN Warning
PIN WARN
Time before PIN expiry after which a warning will be
displayed. (1–14 days)
5 days
SPC42/52/53/63 – Installation & Configuration Manual Engineer programming via the browser