Add Add conditions for the trigger. Click this button to add one or more conditions for the selected trigger.
See Trigger conditions below.
Trigger conditions
The following table lists the trigger conditions and the associated States, Outputs, Events, or
Communication.
Trigger
condition
States, Outputs, Events, or Communications
Zone The trigger is ON if the following conditions are satisfied (i.e. a logical AND operation is
performed): The trigger is ON if the configured zone is in one of the following states - Open,
Close, Short, Disconnected, Tamper, Bypass, Inhibited, or Alarm.
Door The trigger is ON if the any of the following door options are configured: Entry granted,
Entry denied, Exit granted, Exit denied, Door open too long, Door left open, Door
forced open, Door normal, Door Locked, Door unlocked, Interlocked, and Door
Buzzer
Output The trigger is ON if the system output is in the configured state, which can be On or Off:
System Output, Mapping gate, Area Output.
System The trigger is ON for the chosen system event and ID. IDs are: System Reboot,
Overcurrent, Engineer Access, Manufact. Access, XBUS cable fault, Xbus faults.
Time Trigger the trigger is on at the specific time entered in the box provided, in the
format hh:mm.
User Wireless Fob this condition can be configured for a particular user or for any user. With
this configuration, if the configured user (or any user) presses the ‘*’ key on the FOB, it will
cause an instantaneous pulse OFF/ON/OFF. This only applies for FOBs that have been
registered with the system.
Wireless Fob Panic this condition can be configured for a particular user or for any user.
With this configuration, if the configured user (or any user) presses the ‘*’ key on the FOB
Panic, it will cause an instantaneous pulse OFF/ON/OFF. This only applies for FOB Panics
that have been registered with the system.
Keypad Pin this condition can be configured for a particular user or for any user. With this
configuration, if the configured user (or any user) enters a valid PIN, or presents a
configured PACE, it will cause an instantaneous pulse OFF/ON/OFF.
Access card the trigger is activated when the selected user logs in using an access card.
Web Access the trigger is activated when the selected user logs in through the web
browser.
Keypad Access the trigger is activated when any user logs into the selected keypad.
Indicator Access the trigger is activated by a specific function key..
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the browser