Chapter6 Troubleshooting
164
Fault
display
Name of
protection
Possible reasons of fault Actions
OC2
Over current
in Dec process
Too short decelerating
time
Inertia torque of the
load is big.
Too low inverter’s
power
Output load of the
inverter is short
circuited
Increase decelerate time
Add appropriate braking
component
Select a high-power
inverter
Check resistance of the
motor’s winding; check
insulation of the motor
OC3
Over current
in
constant-speed
Operation
Abnormity Load
Too short accelerating/
decelerating time setting
Low voltage of power
supply
Too low inverter’s
power
Output load of the
inverter is short
circuited
Check the load
Add accelerate/decelerate
time properly
Check input power supply
Select the inverter with
higher power
Check resistance of the
motor’s winding; check
insulation of the motor
Ou1
Over Voltage
in acceleration
process
Abnormity Input
voltage
Too short accelerating
time setting
Stall point of
overvoltage is too low
Check input power
supply/ the setting of
detection level
Increase accelerating
time.
Increase stall point
overvoltage
Ou2
Over voltage
in
deceleration
process
Abnormity input
voltage
Too short decelerating
time setting
Inertia torque of the
load is big
Stall point of
overvoltage is too low
Check input power
supply/ the setting of
detection level
Increase decelerating time
properly
Add appropriate braking
component
Increase stall point
overvoltage