Chapter6 Troubleshooting
165
Fault
display
Name of
protection
Possible reasons of fault Actions
Ou3
Over voltage
in constant
speed
Operation
Abnormity input
voltage
Too short accelerating/
decelerating time setting
Inertia torque of the
load is big
Stall point of
overvoltage is too low
Check input power
supply/ the setting of
detection level
Increase decelerating time
properly
Add appropriate braking
component
Increase stall point
overvoltage
GF Ground Fault
Grounding current of
output side exceeds
specified value
Check whether the
insulation of the motor
become bad
Check whether the cable
connecting the inverter
and the motor is damaged
OH1
Heat sink
overheat
Ambient temperature is
too high
Obstruction of
ventilation channel
Cooling Fan does not
work
Lower the ambient
temperature
Clean the ventilation
channel
Replace the cooling fan
OL1
Motor
overload
Inverters output exceed
the over loading value
of the motor
Improper V/F curve
Low AC supply voltage
Common motor has
operated with heavy
load at low speed for a
long time
Load changes fast
Reduce the load
Adjust V/F curve and
torque boost
Check the AC supply
voltage
Use a special motor if the
motor is required to
operate for a long time
Check the load.