186 en | Points Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
24 Hour, Fire, Gas, and AUX AC Point Types, Single EOL Circuit Style, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open I T I T I T S T S S
Armed Short I I T T I T T S S S
Disarmed Open I T I T I T S T S S
Disarmed Short I I T T I T T S S S
Key: I = instant alarm, S = supervisory alarm, T = trouble, blank = no response
Example: Point Type = 24-hour and Point Response = 8. 24-hour point with supervisory
response when open and a trouble response when shorted.
24 Hour, Fire, and Gas Point Types, Dual EOL Circuit Style, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open/
Short
T I T I
Armed Fault I I S S
Disarmed Open/
Short
T I T I
Disarmed Fault I I S S
Key: I = instant alarm, S = supervisory alarm, T = trouble, blank = no response
Example: Point Type = 24-hour and Point Response = 2. 24-hour point with supervisory
response for fault and a trouble response for open or short.
Notice!
For Dual EOL Circuit Style, purchase second 1kΩ EOL separately
Order ICP-1K22AWG-10, package of 10 resistors.
Notice!
Control panel and B208 Octo-input firmware requirements for Dual EOL
To use the Dual EOL Circuit style, verify the control panel firmware is v3.01 or greater.
If you are using a B208 Octo-input Module, verify the module firmware is v2.1.1 or greater.
24 Hour, Fire, and Gas Point Types, No EOL Circuit Style, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Fault I T S
Disarmed Fault I T S
Key: I = instant alarm, S = supervisory alarm, T = trouble, blank = no response
Example: Point Type = 24-hour and Point Response = 2. 24-hour point with supervisory
response for fault and a trouble response for open or short.