D-19
Scanner
®
2000 microEFM Appendix D
Flow Run 1 Conguration
Register
(Decimal)
Register
(Hex) Description
Data
Type Access Default
3004 BBC FR1 Flow Rate Calculation
(See denition.)
U16 R/W 0
3005 BBD FR1 Override Enable
0 - Disabled
1 - Enabled
U16 R/W 0
3006 BBE FR1 Fluid Properties
(See denition.)
U16 R/W 3000
3007 BBF FR1 Fluid Property Calculation
(Number of ow rate calculation
periods before each uid property
calculation)
U16 R/W 1
3008 BC0 FR1 Material Type: Pipe
0 - Stainless Steel (304/316)
1 - Carbon Steel
2 - Monel
3 - Brass
4 - Inconel
5 - Nickel
6 - HastC22
7 - Titanium
U16 R/W 1
3009 BC1 FR1 Material Type: Plate
0 - Stainless Steel (304/316)
1 - Carbon Steel
2 - Monel
3 - Brass
4 - Inconel
5 - Nickel
6 - HastC22
7 - Titanium
U16 R/W 0
3010 BC2 FR1 Tap Type
(See denition.)
U16 R/W 0
3011 BC3 FR1 Static Pressure Selection U16 R/W 8000
3012 BC4 FR1 Differential Pressure Selection U16 R/W 8000
3013 BC5 FR1 Process Temperature Selection U16 R/W 8000
3014 BC6 FR1 Turbine Source U16 R/W 0
3015 BC7 FR1 Mass Units U16 R/W 601
3016 BC8 FR1 Energy Units U16 R/W 701
3017 BC9 FR1 Override Value FP R/W 0.00
3019 BCB FR1 Fail Value FP R/W 0.00
3021 BCD FR1 Low Flow Cutoff FP R/W 0.00
3023 BCF FR1 Low Cutoff FP R/W 0.00
3025 BD1 FR1 Base Temperature FP R/W 60.00 Deg F
3027 BD3 FR1 Base Pressure FP R/W 14.73 psi
3029 BD5 FR1 Atmospheric Pressure FP R/W 14.73 psi
3031 BD7 FR1 Pipe Size FP R/W 2.067 in.