MT
6.6.3 Remote Control Settings (ARC/RSM)
6.6.3.1 ARC Enable
Parameter Possible Values Default Rev HHP Lite Std Adv
ARC Enable No / Yes No -,A,C -
Yes – The user can use the ARC when it is present in the DX System.
No – The ARC is not operational, even when it is present in the DX System.
Note:
For version '–' and 'A':
If ARC Enable is set to 'Yes', set
Joystick Actuators
109
(6.6.1.8) to 'No'.
Otherwise the ARC will not work correctly.
For Version 'C':
ARC Enable and Joystick Actuators can both be set to 'Yes'. If both
are set to 'Yes', the user can use either the joystick or the ARC to
operate the actuators. However,
during the operation of an actuator
the user can not switch between the ARC and the joystick. Using the
ARC and the joystick simultaneously to operate the same actuator
will cancel the actuator operation that is in progress.
6.6.3.2 ARC Always Drives Actuators 1&2
Parameter Possible Values Default Rev HHP Lite Std Adv
ARC Always Drives
Actuators 1&2
No / Yes Yes C -
Yes – The ARC always drives actuator 1 and 2 with its top four switches.
No – The top four switches of the ARC can be used as a switched joystick,
if the
Joystick Source parameter (5.3.8.7) has the value 'ARC'.
6.6.3.3 ARC Drives Actuators 1&2 in Profile 0
Parameter Possible Values Default Rev HHP Lite Std Adv
ARC Drives Actuators 1&2
in Profile 0
No / Yes Yes C -
Yes – The ARC drives actuator 1 and 2 with its top four switches in Drive Profile 0,
but works as a switched joystick in other Drive Profiles, if the
ARC Always Drives Actuators 1&2 parameter (6.6.3.2) has the value 'No'.
No – The ARC works always as configured with the
ARC Always Drives Actuators 1&2 parameter.