5.3.8.4 Allow Non-Driving Profile
Parameter Possible Values Default Rev HHP Lite Std Adv
Allow Non-Driving Profile No / Yes No -,A,C -
Enables Drive Profile 0.
Drive Profile 0 has all parameters set the same as Drive Profile 1, but it prevents the
powerchair from driving. This profile can be useful during the operation of actuators,
because it makes sure that the powerchair does not suddenly start to move after the
actuator operation is completed.
Note:
Some Master Remotes (for example the G90 and G91) automatically
disable driving when the actuator mode is entered. These Remotes
do not have Drive Profile 0, and the value of Allow Non-Driving Profile
is ignored. Refer to the manual of the Remotes in question for more
details.
5.3.8.5 Sleep Timeout
Parameter Possible Values Default Rev HHP Lite Std Adv
Sleep Timeout 1 – 60 min 5 min -,A,C -
If sleep mode is enabled with the
Sleep Mode Enable parameter (see section 5.3.9.8),
Sleep Timeout sets the number of minutes of inactivity after which the DX System goes
to sleep.
Sleep Timeout can be set separately for each Drive Profile.
5.3.8.6 Soft-Start Time
Parameter Possible Values Default Rev HHP Lite Std Adv
Soft-Start Time 0 – 1000 ms 0 ms A,C -
Soft-Start Time sets the time during which
Soft-Start Acceleration is active.
Soft-Start Acceleration (see 5.3.9.2) temporary reduces the acceleration rate when
the chair starts driving from a standstill. This reduces the jerk when starting, particularly
with high acceleration rates or high load compensation settings.
Soft-Start Time can be set separately for each Drive Profile.
If Soft-Start Acceleration is not enabled, the value of the Soft-Start Time parameter is
ignored.
See also section 5.3.1.3:
Acceleration and deceleration.
GBK60348
: Issue 1 – October 2007
82