Firmware V3.13
21.04.2021
201/466
Menü2-2-1Zone1
DEFROST 1 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 8 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost and
cooling
0..15 0 min
M/S Degiv.Fct. XXX Configuration of the defrost via CAN bus function. For
details see chapter Master/slavemode–defrost
synchronisation via CAN bus.
OFF,
MASTR, SLAVE
OFF
M/S CAN Adr. XXX Selection of the controller (1..99) participating in the
defrostviaCANbuswhichisthemaster.“--“,ifthis
controller is itself master (Parameter M/S Degiv.Fct.. =
MASTR)
---, 1..99
DS-Function XXX Configuration of the defrost sequenz function (DS). For
details see chapter Defrost sequenz (DS) via CAN bus.
OFF,
MASTR,
SLAVE
OFF,
DS-Group XXX Selection of which group a defrost sequenz of this
controller (1..99) belongs to
---, 1..99
DS-Master XXX Selection of which controller (1..99) participating in the
defrostsequenzisthemaster.“--“,ifthiscontrolleris
itself the master (Parameter DS-Function = MASTR)
---, 1..99
DS-Wait time XXXm Wartezeit der Folgeabtauung 0..127 1 min