EasyManua.ls Logo

ECKELMANN Case Controller UA 4 E Series - Page 202

ECKELMANN Case Controller UA 4 E Series
466 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware V3.13
21.04.2021
202/466
Menu2-2-2Zone2
DEFROST 2 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 8 °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
Menu 2-2-3 Zone 1T Toggle
DEFROST 1A POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 5 °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
Menü2-2-4Zone2UUmschalt.
DEFROST 2A POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 5 °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
Menu 2-3 Not used with this controller type.

Table of Contents

Related product manuals