Menu 2-2-1 Zone 1
DEFROST 1 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 8 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15
0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
M/S Degiv.Fct. XXX Configuration of the defrost via CAN bus function.
For details see chapter Master/slavemode–defrost
synchronisation via CAN bus.
OFF,
MASTR,
SLAVE
OFF
M/S CAN Adr. XXX Selection of the controller (1..99) participating in the
defrost via CAN bus which is the master.
“--“,ifthiscontrollerisitselfmaster
(Parameter M/S Degiv.Fct.. = MASTR)
---, 1..99 --
DS-Function XXX Configuration of the defrost sequenz function (DS).
For details see chapter Defrost sequenz (DS) via
CAN bus.
OFF,
MASTR,
SLAVE
OFF
DS-Group XXX Selection of which group a defrost sequenz of this
controller (1..99) belongs to.
---, 1..99 --
DS-Master XXX Selection of which controller (1..99) participating in
the defrost sequenz is the master.
“--“,ifthiscontrollerisitselfthemaster
(Parameter DS-Function = MASTR)
---, 1..99 --
DS-Wait time XXXm Wait time for the defrost sequenz 0..127 1 min
Menu 2-2-2 Zone 2
DEFROST 2 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 8 °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 3 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 5 min