Firmware V3.13
21.04.2021
397/466
Menu 2-2-1 Zone 1
DEFROST 1 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 -- °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
Menu 2-2-2 Zone 2
DEFROST 2 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 -- °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
Menu 2-2-3 Zone 1T Toggle
DEFROST 1A POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 -- °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
Menu 2-2-4 Zone 2T Toggle
DEFROST 2A POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 -- °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min