15.6.4 Replacing an M.2 SSD
Upgrade and Repair Unit
(URU)
Hardware: 30 minutes
Software: 15 minutes
Tools: Phillips PH2 / (+) No. 2 screw driver (for cover 2)
If maintenance work involving parts replacement and expansion is
performed in an environment where Windows Server is installed,
reauthentication of Windows Server may be necessary. If re-
authentication is required, inform the customers or system engineer
.
Preliminary steps
"Locating the defective server" on page 97
.
If applicable, "Removing the front cover with lock" on page 45.
"Shutting down the server" on page 46.
"Disconnecting the power cord" on page 47.
"Getting access to the component" on page 48.
Remove the riser modules, see "Removing a riser module" on page 63.
"Removing the fan cage" on page 64.
"Removing the air duct 1 (top system board)" on page 68.
"Removing the top system board carrier" on page 73.
"Removing the OCP air duct" on page 70.
Replacing the M.2 SSD
Remove the defective M.2 SSD, see "Removing the M.2 SSD" on page 357.
Install the new M.2 SSD, see "Installing the M.2 SSD" on page 353.
System board and components
RX4770 M6 Upgrade and Maintenance Manual 359