4.1 PLC Connection 4-3
MX200
Make the following settings on the front panel. For more information, refer to the PLC manual issued by the manufacturer.
LOAD connector
(Underlined setting: default)
ASCII connector
(Underlined setting: default)
Station number
Make the following setting on the front panel.
(Underlined setting: default)
Calendar
This model is equipped with a calendar function; however, the calendar data cannot be written from the V series. Thus, time
correction must be performed on the PLC side.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Communication Setup Mode Setting Remarks
LOAD
connector
setting
Item 0: Address setting
1
to 63 (DEC): 1 to 63
7F(HEX): 127
Settings can also be made in the
PLC application software.
For more information, refer to
the PLC manual issued by the
manufacturer.
Item 1: Baud rate
48: 4800 bps
96: 9600 bps
192: 19200 bps
Item 2: Communication
mode
8E1: data length 8 bits, even parity, 1 stop bit
8n2: data length 8 bits, without parity, 2 stop bits
Communication Setup Mode Setting Remarks
ASCII
connector
setting
Item 0: Baud rate
48: 4800 bps
96: 9600 bps
192: 19200 bps
Settings can also be made in the
PLC application software.
For more information, refer to the
PLC manual issued by the
manufacturer.
Item 1: Data length
7b: 7 bits
8b: 8 bits
Item 2: Parity bit
EP: Even
oP: Odd
nP: None
Item 3: Stop bit
1S: 1 bit
2S: 2 bits
Item 4: Connector usage Ldr: LOAD connector
Item 5: Connecting
device selection
CPL: Yamatake communication support device
Item 7: RTS control non: No RTS control
Item 8: Signal level
selection
232: RS-232C
MX Address Display/Setting Mode Setting Remarks
Addr 1
to 63
Device Memory TYPE Remarks
R (data register) 00H R910, 929, 930, 956 to 987, 994 to 997: Read only
M (auxiliary relay) 01H M920 to 940, 970 to 990: Read only
L (latch relay) 02H
X (input relay) 03H
Y(output relay) 04H
TP (timer/current value) 05H Data format: BCD
TS (timer/set value) 06H Data format: BCD
CP (counter/current value) 07H Data format: BCD
CS (counter/set value) 08H Data format: BCD
T (timer/contact) 09H
C (counter/contact) 0AH
P (link register) 0BH

Table of Contents

Other manuals for Hakko Electronics Monitouch V9 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hakko Electronics Monitouch V9 Series and is the answer not in the manual?

Hakko Electronics Monitouch V9 Series Specifications

General IconGeneral
BrandHakko Electronics
ModelMonitouch V9 Series
CategoryMonitor
LanguageEnglish

Related product manuals