1-12 1. Overview
- RS-485 (2-wire system)
MJ1/MJ2
RS-232C connection
Use Hakko Electronics’ cable “V6-TMP” (3, 5, 10 m) as a communication cable.
The maximum length of wiring is 15 m.
* The maximum length varies depending on the connected device. Check the specifications for each device.
Connect a shielded cable to either the V9 series or the connected device. Connect the cable to the FG terminal on the
backside of MONITOUCH.
If noise disturbs communications, connect a shielded cable to both the V9 series and the connected device.
Name
1
No.
2
3
4
-RD
-SD
+SD
5SG SG
FG
+RD
FG
Dsub 9 (Male)
CN1
5
9
1
6
Shielded
RS-485 port of the
connected device
Send/receive data (+)
Send/receive data ()
SG
Name
No.
RJ - 45
7
8
5
RD
SD
SG
FG
MJ1/2
12345678
RS-232C port of the
connected device
Send data
Receive data
Shielded
SG
FG
Name
No.
RJ - 45
7
8
5
RD
SD
SG
FG
MJ1/2
12345678
Shielded
RS-232C port of the
connected device
Send data
Receive data

Table of Contents

Other manuals for Hakko Electronics Monitouch V9 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hakko Electronics Monitouch V9 Series and is the answer not in the manual?

Hakko Electronics Monitouch V9 Series Specifications

General IconGeneral
BrandHakko Electronics
ModelMonitouch V9 Series
CategoryMonitor
LanguageEnglish

Related product manuals