20-6 20. Hitachi Industrial Equipment Systems
PORT1
Procedure
1. Turn the PLC off and set the baud rate using the DIPSW.
2. Turn the power on and check the value set for “ Special internal output: WRF01A”.
3. When the transmission control protocol has correctly been selected, setting is completed. If it is wrong, set a correct
value.
4. Set the bit “R7F6” (setting write request) to save the setting in the flash memory.
* It is not necessary to make the setting again upon next power-up once the setting has been saved in the flash memory.
Note that the ladder tool cannot be connected when the setting has been saved using the transmission control protocol
2.
DIPSW
Special internal output: WRF01A
PORT2
Procedure
1. Check the value set for special internal output “WRF03D”.
2. When the setting, such as transmission control protocol or baud rate, has correctly been defined, the setting is
completed. If it is wrong, set a correct value. See “User Setting” described in “ Special internal output: WRF03D”.
3. Check that the value set for WRF03D has been changed to the one shown in the “System Setting” column.
4. Set the bit “R7F6” (setting write request) to save the setting in the flash memory.
* It is not necessary to make the setting again upon next power-up once the setting has been saved in the flash memory.
Special internal output: WRF03D
SW1 SW2 SW3 SW4 Baud Rate
ON OFF ON OFF 38.4 kbps
ON OFF OFF OFF 19.2 kbps
OFF OFF ON OFF 9600 bps
OFF OFF OFF OFF 4800 bps
Device Memory Setting Contents
WRF01A
H0000 Transmission control protocol 1
H8000 Transmission control protocol 2
Device Memory Setting
WRF03D
Setting example
15 14 13 12 8 7 0
a b c d Station number 00 to 31 (BCD)
Baud rate
d Baud Rate
00000 4800 bps
00001 9600 bps
00010 19.2 kbps
00011 38.4 kbps
Station number
0: Without station number
1: With station number
Bit setting 1: Set (when setting completed, the system sets this value to “0”.)
Transmission control protocol
0: Transmission control protocol 1
1: Transmission control protocol 2
User Setting System Setting Interface Baud Rate
H8300 H0300 Transmission control protocol 1
38.4 kbps
HC300 H4300 Transmission control protocol 2
HA300 H2300 Transmission control protocol 1 with port
HE300 H6300 Transmission control protocol 2 with port