4 Individual remote controls
PC-ARF
TCGB0106 rev.0 - 12/2014
113
4
Defrost
• Defrost Operation
“DFR” is turned ON during the defrosting.
The indoor fan is stopped though the indication is not changed. The louver is
xed at the horizontal position. However, the louver indication of LCD continues
to activate.
A/C
LOUV. ADJ
DFR
MODE SPEED LOUV.
HEAT
MED
TEMP
Meeting Room
• Operation Stoppage during Defrosting Operation
The RUN indicator (Green) is turned OFF when the operation is stopped during the defrosting.
However, the operation continues with “DFR” indication, and the unit is stopped after the defrost operation is nished.
Operation control
• Supplying Electrical Power
“HOT-ST” is turned ON when the electrical power is turned ON.
In this case, the compressor is under preheating. The operation may not be
available for max 4 hours. Do not turn off the outdoor unit electrical power during
the high season for Cooling/Heating operation.
A/C
HOT-ST
LOUV. ADJ
MODE SPEED
HEAT
MED
TEMP
Meeting Room
• During Hot Start (Heating Operation Only) “HOT-ST” is turned ON.
A/C
LOUV.
HOT-ST
LOUV. ADJ
MODE SPEED
HEAT
MED
TEMP
Meeting Room
• Different Operation Mode
The operation mode set by the remote control switch is different with the out-
door unit operation mode. (Except for the heat recovery system models.)
The indication of the actual operation mode ashes.
Indication when “COOL” operation is set by the remote control switch at the
outdoor unit “HEAT” operation.
A/C
HEAT
LOUV.
LOUV. ADJ
COOL
MED
TEMPMODE SPEED
Meeting Room