6 Building air conditioning controls
CSNET Manager LT/XT
TCGB0106 rev.0 - 12/2014
531531
6
6.2.4.5 Local software conguration
After conguring the CSNET Manager interface you should begin the conguration of the system. To install the RCS
Web instead of CSNET Manager read the chapter “6.2.5.4 RCS Web”. Remember that RCS Web is a reduced version of
CSNET Manager with only remote control functions but more user-friendly for a non-expert user.
NOTE
CSNET Manager needs at least the following to be congured:
• Local software conguration (see next page)
• Area tree (see chapter “Area tree”)
• Conguration of the unit (see chapter “Unit Setting”)
• Auto Cool/Heat (see chapter “Auto cool/heat”)
• Fan stop heating during thermo-off (see chapter “Fan stop heating during thermo-off”)
We recommend conguring the other points indicated in the manual at the same time, although this can be done later.
After switch ON the CSNET Manager, a page appears in which must be specied the language you want to use. The same
screen shows a timer (this can be congured later), which runs down to zero and then runs the software in the selected
language.
Wait 10 seconds or press the OK button, CSNET Manager will show the Initial Page.
NOTE
Please be aware that pressing the ON/OFF button of CSNET Manager forces a complete shut down