6 Building air conditioning controls
CSNET Manager LT/XT
TCGB0106 rev.0 - 12/2014
581581
6
6.2.4.7 Operation with slave CSNET Managers
One CSNET Manager can read units from another CSNET Manager. This second CSNET Manager could have more than
one devices congured, this means that to keep an unique identier of the units, CSNET Manager show the CS Port as
follow:
[Slot on the current CSNET Manager].[Slot inside the remote CSNET Manager]
On the following image we can see an example of that:
This addressing is used along the screens to make easy to identify the remote units.
Not all the functions can be managed through a remote CSNET Manager, the following table shows which ones can be
done:
Display data from remote
CSNET Manager
Modied to remote CSNET
Manager
Work locally with CSNET
Manager remote units
IU Table/ IU Matrix – send
orders
O O O
Building Layout with File X X X
Timer X X O
Historical data O - -
Power consumption O - -
Web O O -
Mail alarm X X O
Fidelio X X O
Modbus Server X X O
Unit conguration O O X
Auto C/H O O X
Fan stop heating O O X
Cold Draft O O X
OU options O O X
Power meter X X X
O = available, X = not available, - = do not apply
NOTE
A combination of one CSNET Manager and one HC-A64NET is who controls the units. In case of a remote CSNET Manager viewing
another one, it never should be stopped the CSNET Manager – HC-A64NET that owns the Indoor units.